Equipment and function
• Manual power adjustment with 3 speed stages.
• Pumps with 1~ motor:
- P2 up to 90 W: Internal protection against unacceptably high winding temperatures.
- * P2 = 180 W: Full motor protection by thermal winding contacts in combination with tripping unit.
• Pumps with 3~ motor:
- P2 up to 90 W: Internal protection against unacceptably high winding temperatures.
- P2 ≥ 180 W: Full motor protection with integrated trip electronics. * Mains connection 3~230 V with optional switching plug.
• Cataphoretic-coated pump housing for optimal corrosion protection.
• Combination flange PN 6/PN 10 (with DN 40 to DN 65).
• Thermal insulation shells for heating applications.
• Additional functions with retrofittable Protect Module C:
- SSM fault signal as potential-free normally closed contact.
- SBM run signal as potential-free normally open contact.
- Overriding Off; control input by external potential-free contact (normally closed contact).
- Blockage detection.
- Full motor protection with built-in tripping.
- Fault acknowledgement.
- Dual pump management. (two single pumps installed in parallel): Main/standby mode (automatic fault-actuated switchover/time-dependent pump cycling.
Materials
- Pump housing: Grey cast iron (EN-GJL-200)
- Impeller: Plastic (PP - 50% GF)Pump shaft: Stainless steel (X46Cr13)Bearing: Carbon, metal impregnated.
Approved fluids (other fluids on request)
- Max. volume flow: 10m3/h
- Max. delivery head: 1m
Permitted field of application
Temperature range at max. ambient temperature +40 °C: -20 up to +130 (in short-term operation 2 h: +140) (for applications with Wilo-Protect-Module C: -20 to +110)°C
Pipe connections
- Threaded pipe union: Rp 1
- Thread: G 1½
- Overall length: 180 mm
Includes 22mm Cast Iron Unions
Motor/electronics
- Emitted interference: EN 61000-6-3
- Interference resistance: EN 61000-6-2
- Protection class: IP X4D
- Insulation class: H
- Mains connection: 1~230 V, 50 Hz
- Mains frequency: 50 Hz
- Nominal motor power: 180 W
- Speed: 2400 / 2550 / 2700 rpm
- Power consumption 1~230 V: 335/ 385/ 390 W
- Current at 1~230V: 1.72 / 1.87 / 1.90 A
- Motor protection: Optional SK 602N/622N tripping unit, Protect module C
- Threaded cable connection: 2x13.5
Please note that stock availability is subject to prior sales. Prices exclude delivery.
Important:
All solar products, power systems, water heating and gas products and their components must be installed by appropriately qualified personnel. All installations must adhere to local wiring regulations and standards. Sustainable Online will not be held liable for any product malfunctions as a result of incorrectly installed systems.